Building valves - Expansion valves - Tests and requirements
Status:
Valid
Buy this standard
StandardSwedish standard
·
SS-EN 1491:2022
Building valves - Expansion valves - Tests and requirements
Subscribe on standards with our subscription service. When you use our service you can be assured the latest editions and easy access.
Read more about SIS Subscriptions
This document specifies dimensions, materials and performance requirements (including methods of test) for expansion valves, of nominal sizes from DN 15 to DN 32, having working pressures ) from 0,1 MPa (l bar) to 1,0 MPa (10 bar).
Expansion valves are intended for fitting to the cold potable water supply of storage water heaters, having a maximum distribution temperature of 95 °C, for all energy sources.
Expansion valves do not control the temperature and alone do not constitute the protection required for storage water heaters. Expansion valves limit pressure, in the water heaters to what they are fitted, that is produced by thermal expansion of the water.
NOTE The use of the device specified in this document does not override the need to use controls (e.g. thermostats and cut-outs) which act directly on the power sources of water heaters (for more information see Annex A).